Cat7 Ethernet Cable

Cat7 is classified as Class F. Documented frequency, channel length, Ethernet application support and construction considerations, with the conditions attached to every figure.

Key specifications

ISO/IEC class
Class F
Maximum frequency
600 MHz
Maximum channel
100 m
Permanent link
90 m
ANSI/TIA recognition
Not a TIA category
ISO/IEC recognition
Recognized

Frequency vs throughput. MHz is a cabling performance parameter, not Ethernet throughput. Channel length includes the permanent link plus patch and equipment cords.

Standards recognition

Cat7 is ISO/IEC Class F, not an ANSI/TIA category.Cat7 is recognized by ISO/IEC 11801 but not by ANSI/TIA-568. Full channel performance requires an appropriate ISO-compliant connector system — a product sold as "Cat7 RJ45" should not be assumed to deliver the full ISO class without evidence.

Full Class F channel performance is associated with ISO-compliant connector systems such as GG45 or TERA. A product advertised as Cat7 with ordinary RJ45 terminations requires careful qualification; do not assume full Class F performance.

Ethernet speed and distance

The category's baseline application is10GBASE-T at100 m, as represented in the category reference data. Application-specific conditions still apply.

Documented distance records for Cat7. Status uses the site's four-state label system.
Ethernet standardDistanceTypeStatusConditions
10GBASE-T0–100 mChannelISO Class F baselineISO Class F compliant shielded channel and appropriate connector system.

Supported Ethernet applications

No application records are currently available for this category.

Class F cabling was designed to support 10 Gigabit Ethernet over 100 m. Higher category frequency does not itself create a faster Ethernet PHY.

Construction and connectors

Class F uses fully shielded cabling; commonly described as S/FTP with individual pair foil and an overall braid.

Full Class F channel performance is associated with ISO-compliant connector systems such as GG45 or TERA. A product advertised as Cat7 with ordinary RJ45 terminations requires careful qualification; do not assume full Class F performance.

Cable category alone does not specify every construction detail. Check the actual cable datasheet, conductor material, shielding, connector compatibility and installation requirements. See thecable construction reference.

Power over Ethernet considerations

Category designation alone does not guarantee that a cable installation is suitable or safe for every PoE load. The three considerations below are documented in the site's PoE cable guidance dataset — each carries specific conditions that the installer must confirm against the product datasheet and the applicable remote-powering guidance.

Conductor material

Use compliant copper conductors for standards-based PoE cabling; do not assume copper-clad aluminum (CCA) cable is suitable.

Confirm the cable's applicable listing and conductor resistance. Avoid recommending CCA for permanent structured cabling or higher-power PoE.

Thermal conditions

PoE current causes resistive heating in cable conductors. Larger bundles, higher ambient temperature, higher current, smaller conductors and conduit can increase thermal risk.

Bundle size must be evaluated using applicable TIA/ISO/CENELEC remote-powering guidance and the actual cable construction, current, ambient temperature and installation method.

Channel length and power budget

The common structured-cabling channel limit is 100 m, but the usable PD power is affected by channel resistance and power loss.

The 100 m channel length does not guarantee a particular power budget for every cable, connector, temperature or bundle configuration.

See the Power over Ethernet reference for the full standards and guidance, and the product datasheet for conductor AWG, DC resistance and bundling guidance for this specific cable.

Important limitations

Explain that Cat7 is an ISO/IEC category/Class F, not an ANSI/TIA-recognized category. Avoid the unqualified phrase 'TIA Cat7'.

The figures on this page describe documented reference conditions. They are not a substitute for testing an installed channel or checking the applicable standards and product documentation.