Cat5e Ethernet Cable
Cat5e is classified as Class D. Documented frequency, channel length, Ethernet application support and construction considerations, with the conditions attached to every figure.
Key specifications
- ISO/IEC class
- Class D
- Maximum frequency
- 100 MHz
- Maximum channel
- 100 m
- Permanent link
- 90 m
- ANSI/TIA recognition
- Recognized
- ISO/IEC recognition
- Recognized
Frequency vs throughput. MHz is a cabling performance parameter, not Ethernet throughput. Channel length includes the permanent link plus patch and equipment cords.
Ethernet speed and distance
The category's baseline application is1GBASE-T at100 m, as represented in the category reference data. Application-specific conditions still apply.
| Ethernet standard | Distance | Type | Status | Conditions |
|---|---|---|---|---|
| 1000BASE-T | 0–100 m | Channel | Baseline | Compliant Cat5e channel and correctly installed/terminated components. |
Supported Ethernet applications
| Application | Link rate | Recorded reach | Status | Conditions |
|---|---|---|---|---|
| 100BASE-TX | 100 Mb/s | 100 m | Documented | Compliant balanced twisted-pair channel; installation and termination must meet the applicable cabling requirements. |
| 1000BASE-T | 1 Gb/s | 100 m | Documented | Compliant four-pair channel. |
| 2.5GBASE-T | 2.5 Gb/s | 100 m | Conditional | IEEE/NBASE-T use-case guidance permits operation over installed Cat5e; actual channel performance depends on alien crosstalk, installation, bundling and test results. |
| 5GBASE-T | 5 Gb/s | — | Not assured | Do not publish a universal 100 m Cat5e claim. Some installations may work, but this batch does not assign a guaranteed reach. |
| 10GBASE-T | 10 Gb/s | — | Not documented | Not listed as a supported cabling category in the cited application guidance. |
2.5GBASE-T and 5GBASE-T may operate over compliant installed Cat5e in qualifying circumstances; do not state as a blanket guarantee.
Construction and connectors
Can be supplied in shielded or unshielded variants; category alone does not determine shielding.
Commonly terminated with 8P8C modular connectors commonly called RJ45.
Cable category alone does not specify every construction detail. Check the actual cable datasheet, conductor material, shielding, connector compatibility and installation requirements. See thecable construction reference.
Power over Ethernet considerations
Category designation alone does not guarantee that a cable installation is suitable or safe for every PoE load. The three considerations below are documented in the site's PoE cable guidance dataset — each carries specific conditions that the installer must confirm against the product datasheet and the applicable remote-powering guidance.
Conductor material
Use compliant copper conductors for standards-based PoE cabling; do not assume copper-clad aluminum (CCA) cable is suitable.
Confirm the cable's applicable listing and conductor resistance. Avoid recommending CCA for permanent structured cabling or higher-power PoE.
Thermal conditions
PoE current causes resistive heating in cable conductors. Larger bundles, higher ambient temperature, higher current, smaller conductors and conduit can increase thermal risk.
Bundle size must be evaluated using applicable TIA/ISO/CENELEC remote-powering guidance and the actual cable construction, current, ambient temperature and installation method.
Channel length and power budget
The common structured-cabling channel limit is 100 m, but the usable PD power is affected by channel resistance and power loss.
The 100 m channel length does not guarantee a particular power budget for every cable, connector, temperature or bundle configuration.
See the Power over Ethernet reference for the full standards and guidance, and the product datasheet for conductor AWG, DC resistance and bundling guidance for this specific cable.
Important limitations
State the 1 Gb/s at 100 m baseline. Do not imply every Cat5e product supports every multi-gigabit PHY at 100 m.
The figures on this page describe documented reference conditions. They are not a substitute for testing an installed channel or checking the applicable standards and product documentation.
Related reference
Sources
- ANSI/TIA-568.2-E: Balanced Twisted-Pair Telecommunications Cabling and Components StandardTelecommunications Industry Association (TIA)
- ISO/IEC 11801-1:2017/Amd 1:2025: Information technology — Generic cabling for customer premises — Part 1: General requirementsISO / IEC (JTC 1/SC 25)
- IEEE Std 802.3-2022: IEEE Standard for Ethernet (incorporating 802.3ab, 802.3an, 802.3bq, and 802.3bz)IEEE Standards Association (IEEE 802.3 Working Group)
- Copper Structured Cabling Design Guide, Issue 10Belden
- Standards Comparison, Version 3.0 / 2024Datwyler IT Infra
- Ethernet Cable Categories Explained: A Brief HistoryFluke Networks
- Network Engineer Tools and Troubleshooting GuideFluke Networks
- ANSI/TIA-568.0-E — Commercial Building Telecommunications Cabling Standard (excerpt)Telecommunications Industry Association (TIA), document hosted by U.S. government procurement source
- Technology Guide: Ethernet Cables and Transceivers OverviewIntel
- Category 6A — The cabling of choice for new installationsCommScope